Control Mode: V/F control, Sensorless Vector Control (SVC)
Overload Capacity: 60s with 150% of rated current, 10s with 180% of rated current.
Speed Adjusting Range: 1:100 (SVC)
Carrier Frequency: 1 kHz ~15.0 kHz.
Frequency Reference Source: keypad, analog input, HDI, serial communication, multi-stage speed, simple PLC and PID setting. The combination of multi-modes and the switch between different modes can be realized.
PID Control Function
Simple PLC, Multi-Steps Speed Control Function: 16 stages speed can be set.
Traverse Control Function
Non-Stop when Instantaneous Power off.
Speed Trace Function: Smoothly start the running motor.
Key: User defined shortcut key can be realized.
Automatic Voltage Regulation Function (AVR):
Automatically keep the output voltage stable when input voltage fluctuating
Up to 25 fault protections: Protect from over current, over voltage, under voltage, over temperature,
phase failure, over load etc.